Bosch Appliances ICP-CC488 Home Security System User Manual


 
ICP-CC488 | Installation Guide | 3.0 System Operations EN | 18
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
5. Press [AWAY].
Two beeps sound and the system returns to the
disarmed state.
The indicators for the selected zones continue to
flash until the next time the system is disarmed.
Example
To manually isolate zones 1, 3, and 4, press:
[STAY][User Code][STAY][1][STAY][3][STAY][4]
[STAY][AWAY]
3.12 Fault Analysis Mode
When a system fault occurs, the FAULT or MAINS
indicator flashes and the codepad beeps once per
minute.
If the AC MAINS supply fails, the MAINS indicator
flashes until the AC MAINS supply is restored. Press
[AWAY] once to acknowledge the fault and stop the
codepad from beeping once every minute.
To enter Fault Analysis Mode to determine a
system fault other than the AC MAINS supply:
1. Press and hold [5] until two beeps sound.
The FAULT indicator remains lit and the STAY
and AWAY indicators flash.
The lit zone indicators indicate the type of fault
that occurred. Refer to Table 15 on page 20.
2. If necessary, hold down the button
corresponding to the indicator to further
determine the fault. Refer to Table 15 on page 20.
3. To exit from Fault Analysis Mode, press
[AWAY].
The STAY and AWAY indicators are
extinguished and the FAULT indicator remains
lit.
3.13 Fault Descriptions
1 – System Fault
The system FAULT indicator lights when any of the
faults listed in Table 14 on page 19 occurs. In Fault
Analysis Mode, hold down [1] to determine the fault
that occurred.
2 – RF Low Battery
This fault occurs when a wireless zone (1 to 16)
reports a low battery condition. In Fault Analysis
Mode, hold down [2] until two beeps sound to light
the indicator for the zone that reported the fault.
3 – Tamper Fail
This fault occurs when a zone becomes open circuit.
In Fault Analysis Mode, hold down [3] until two
beeps sound to display the zone that reported the
fault.
4 – Sensor Watch Fault
This fault occurs when one or more detection devices
fails to detect an intrusion while disarmed for the
time period programmed in Locations 476 and 477
(refer to Section 15.5 Zone Status – Sensor Watch
Reports on page 78). The fault clears when the
faulted zone detects movement and is reset.
In Fault Analysis Mode, hold down [4] until two
beeps sound to show the zone that reported the fault.
5 – RF Sensor Watch Fault
This fault occurs when one or more wireless
detection devices fails to detect an intrusion while
disarmed state for the time programmed in Locations
476 and 477 (refer to Section 15.5 Zone Status – Sensor
Watch Reports on page 78). The fault clears when
the faulted zone detects movement and is reset.
In Fault Analysis Mode, hold down [5] until two
beeps sound to show the zone that reported the fault.
6 – Communication Fail
A communication failure registers when the control
panel fails to communicate with the receiving party
(for example, monitoring company, mobile phone, or
pocket pager).
The communication fault clears when the control
panel successfully reports to the receiving party.
In Fault Analysis Mode, hold down [6] until two
beeps sound to show which communication fault
occurred: 1 – Receiver 1; 2 – Receiver 2.