Bosch Appliances ICP-CC488 Home Security System User Manual


 
ICP-CC488 | Installation Guide | 16.0 Programmable Outputs EN | 72
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
0,12 Entry Warning + Day Alarm Resetting
This output combines Entry Warning and Day Alarm
Resetting so that either of these two events activates
the output.
If the output is activated by Entry Timer 1, Entry
Timer 2, or Entry Guard Timer for STAY Mode, the
output is reset when the Entry Time expires or the
system is disarmed.
If a zone programmed for Day Alarm is activated
when the system is disarmed, the output is reset
when the zone is resealed. You can turn Day Alarm
on and off by holding down [4]. Refer to Section 14.1
Day Alarm Information for programming zones to
operate for Day Alarm.
0,13 Exit Warning + Entry Warning + Day Alarm
Resetting
This output operates when the system is armed,
regardless of whether zones are sealed or unsealed,
until Exit Time expires.
The output operates again during Entry Time and is
reset when Entry Time expires or the system is
disarmed. The output also operates during the Entry
Guard Timer for STAY Mode time.
If a zone programmed for day alarm is activated
when the system is disarmed, the output is reset
when the zone is resealed. You can turn Day Alarm
on and off by holding down [4]. Refer to Section 14.1
Day Alarm Information for programming zones to
operate for Day Alarm.
0,14 Day Alarm Resetting
This output operates when a zone programmed for
Day Alarm is activated. The output is reset when the
Day Alarm zone is resealed. You can turn Day
Alarm on and off by holding down [4]. Refer to
Section 14.1 Day Alarm Information for programming
zones to operate for Day Alarm.
0,15 Day Alarm Latching
This output operates when a zone programmed for
Day Alarm is activated. The output is reset by
pressing [AWAY]. You can turn Day Alarm on and
off by holding down [4]. Refer to Section 14.1 Day
Alarm Information on page 56 for programming zones
to operate for Day Alarm.
If the ICP-CC488 Control Panel is partitioned,
pressing [AWAY] on a CP5 Area Addressable
codepad other than the one to which the zone is
allocated, or pressing [AWAY] on a CP5 Master
Partitioned Codepad does not reset the output. You
can reset only this output on the area codepad to
which the zone is allocated.
1,0 Day Alarm Enabled
This output operates when Day Alarm is enabled.
The output is reset when Day Alarm is turned off.
Refer to Section 14.1 Day Alarm Information on page 56
for programming zones to operate for Day Alarm.
You can turn Day Alarm on and off by holding
down [4]. Three beeps indicate that Day Alarm is
turned on, two beeps indicate that Day Alarm is
turned off. Refer to Section 5.4.7 Turning Day Alarm On
and Off on page 33 for more information.
1,1 Telephone Line Fail
This output operates when the built-in telephone line
fault module detects that the telephone line is
disconnected longer than 40 sec. The output is reset
when the telephone line is restored continuously for
40 sec. This output does not operate unless Option 1
in Location 176 is selected (refer to Section 11.11
Telephone Line Fault Options on page 52).
1,2 Kiss-off Received
This output operates after the control panel
successfully transmitted to the receiving party.
1,3 AUX Power Supply Fail
This output operates when either the 1 A codepad
AUX power supply or the 1 A accessories AUX
power supply fails. The output is reset when the
faulty AUX power supply is reset.
1,4 AC Fail
This output operates when the AC MAINS fails. The
output is reset when the AC MAINS is restored. This
output operates regardless of whether Option 2 in
Location 494 is selected (refer to Section 18.3 System
Options 3 on page 81).
1,5 Low Battery
This output operates when a Dynamic Battery Test
detects the battery failed or the battery voltage is
below 11.2 VDC. The Dynamic Battery Test is
performed every 4 hours after the system is powered
up and every time the system is armed.
This output is reset only after a Dynamic Battery Test
reports that the backup battery voltage is normal.
1,6 Horn Speaker Monitor Fail
If the Enable Monitoring of Horn Speaker option (2)
in Location 492 is selected (refer to Section 18.1 System
Options 1
on page 80), this output operates when the
horn speaker is disconnected. The output is reset
when the horn speaker is reconnected.