American Power Conversion Central Air Conditioning System Air Conditioner User Manual


 
Network Management Card: Quick Configuration
NetworkAIR IR Operation, Maintenance, and Troubleshooting 51
Local access to the control console
You can use a local computer that connects to the NetworkAIR IR System through the serial port on
the control board to access the control console. Whenever possible access the control panel through a
network connection.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable (APC part
number 940-0103) to connect the selected
port to the serial port (J2) on the
controller board. The controller board is
in the right compartment of the electrical
panel.
3. Run a terminal program (such as
HyperTerminal) and configure the
selected port for 2400 bps, 8 data bits, no
parity, 1 stop bit, and no flow control, and
save the changes.
4. Press
ENTER to display the User Name prompt.
5. Use apc for the user name and password.
6. See “Control console” on page 52 to finish the configuration.
The procedure requires the front door and right side (low voltage) of the
electrical panel of the NetworkAIR IR In-row Precision Air Conditioner to be
open, which creates an electrical hazard.
Do not touch components on
the electrical panel, other than
the serial port.