American Power Conversion Central Air Conditioning System Air Conditioner User Manual


 
Operation: View Status Readings
NetworkAIR IR Operation, Maintenance, and Troubleshooting 37
Group status
Path: Main > Status > Group
The Group Status screen includes information about the member Systems of the Group and their
roles.
Group Status. View the assigned role and current state of each System in the Group
Group Run hours. View the run hours for each System in the Group
Reset Local System Run Hours. Reset the run hours of the local System. To reset the run hours of
the other Systems, you must repeat this step at each System’s display interface or Network
Management Card. The service password is required to perform this action.
View Event Log
The event log saves status information and a message each time a change in the System is detected.
Alarms and events are recorded in the log. However, status events (informational) are displayed only
on the active alarms screen.
View Log
Path: Main > View Log
New Events.
The New Events option displays a log of events that have occurred since the last time
the log was checked.
Entire Log. The event log keeps a record of all alarms and events. Each event log entry consists of
four screens of information. The initial screen consists of the following:
The name of the alarm
Its index number in the log and the Module to which it applies
The time and date the event occurred
The name (description) of the event
Use the arrow keys to scroll through the list of events.
To view more details about the event press the
ENTER key. Two more screens display the following:
Supply temperature and humidity
Return temperature and humidity
Output code (for use during service calls)
To move from screen to screen, use the arrow keys.
Clear Log. Erase all events in the log. You must enter the service password to erase the log.