Operation: Set Up Module Control
NetworkAIR IR Operation, Maintenance, and Troubleshooting 19
Reset compressors
Paths: Main > Setup > Module > Main Module > Module Control > Reset Compressors
Main > Setup > Module > Expansion Module > Module Control > Reset
Compressors
The Reset Compressors option resets the compressors after an alarm. The compressors shut down
during a Suction Pressure Low alarm. Use this function to restart the compressors manually when
the alarm condition is resolved.
Low Suction Pressure alarms indicate a problem with the refrigeration
system. Check the event log for other alarms before resetting the
compressors.