Operation: Set Up Contacts and Relays
14 NetworkAIR IR Operation, Maintenance, and Troubleshooting
Action. Set the System controller to respond to the change of status for an input in one of the
following ways:
Output relays
Path: Main > Setup > System # > Input/Output > Output Relays
The Main Module supports up to 16 user-defined output relays. Output relays respond to internal
alarms and events by changing state to notify outside devices.
Relay Out. Choose the relay number to view or modify.
Map. Choose alarms or events to map to this relay:
The first line of the map field displays the location of the event that is mapped to this relay. It
can be a System, Main Module, Expansion Module 1, or Expansion Module 2 event.
The second line displays the name of the event mapped to this relay.
State
Map Description/Function
Status Only Displays the event on the Active Alarms
screen. Status-only events are not logged.
Minor Alarm Activates the Warning LED and the alarm
beeper. It also creates an entry in the event log.
Major Alarm Activates the Alarm LED and the alarm
beeper. It also creates an entry in the event log.
Remote Run/Stop Shuts down the Modules normally, waiting for
delay timers.
Nonessential Lockout Deactivates modes set as nonessential and
continues operation.
Immediate Shutdown Shuts down the Modules immediately. It does
not wait for the blower delay or compressor
timers.
Note
Any input contact and output relay available in this System can be mapped to this relay.