Tyco 4100U-S1 Smoke Alarm User Manual


 
4-2
The following table summarizes the specifications for the SPS.
Table 4-1. SPS Input and Output Specifications
AC Input Specifications
SPS in Basic 4100U-
S1 (4100-9848AU)
240 VAC + 6% -10% @ 50 Hz
2 A Maximum
DC Output Specifications
Voltage
Nominal 28VDC
Minimum: 19.5 VDC Maximum: 32 VDC
Ripple: 2 VDC p-p @ full load (9A)
Total Current (max)
24V Card
24V Aux
Each NAC (total A+B)
9A alarm load. Includes: NACs; +24V Card;
+24V Aux; SPS card including on-board IDNet.
5A non-alarm load. Includes the above
allowances, and allows for battery charging at
high rate.
2A max. See note.
2A max
3A max alarm load
2A max non-alarm load (when used as AUX
24V power).
SPS IDNet Output 30 V or 35 V (see note below)
Battery Charger Specifications
Input Voltage Range 21-33 VDC
Output Float Voltage
27.3 VDC ±200 mV @ 20°C, temperature
compensated at approximately -36mV/°C
(0° C to 50° C)
Supervision Voltages
(nominal at 20°C)
Charger High 28.4Vdc
Charger Low 26.2Vdc
Battery Low 24.3Vdc
Battery Depleted 19.4Vdc
Output Current Limit
1.4 A (For 6.2 – 18 Ah battery)
3.3 A (Default; for 18-110 Ah battery)
Notes:
AC power must be provided to the 4100U-S1 from a dedicated AC branch circuit.
The AC input is supervised wiring.
The AC branch is terminated in the cabinet in the general power output (GPO)
mounted in the expansion bay. The SPS plugs into the GPO via a 3-pin plug and
mains lead.
A mains fail fault is generated when the DC voltage drops below 20.3V (nominally at
mains voltage 204VAC).
Continued on next page
SPS Specifications
Input/Output/Battery
Specifications