Tyco 4100U-S1 Smoke Alarm User Manual


 
G-1
System Capacity 500 points of addressable devices, plus 500 points of
annunciation.
Expansion up to 4 x 4100 legacy cards
up to 4 x 4” x 5” PDI cards
Cabinet Size 1050H x 550W x 280D (mm)
Cabinet Material 1.2mm Zintec
Cabinet Finish Powder coated
Cabinet Colour Cream Wrinkle external, flat black internal trim
Mounting Wall mount
Mains Input 240V AC, +6%, -10%, 50Hz
Internal Power Supply 24V DC @ 9A
Standby Battery 24V sealed lead acid type up 40Ah
Battery Charger 27.3V DC (nominal)
PSU Supervision Charger high/low, Battery low/fail
Temperature -5°C to 45°C
Humidity 10% to 90% RH non-condensing
Refer to Table 4-1 and 4-2 for full SPS specifications.
Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
WALK TEST System Test
4 Operator Access Levels
Event Historical Logging
Device selectable Alarm Verification
Individual Zone Isolate
Addressable device disable/enable
Non-volatile Flash EPROM for field editable program changes
Expansion cards firmware upgraded via download to flash EPROMs
Appendix G
4100U-S1 Specifications
General
Fuses
Firmware Features