Standby Current (A) Alarm Current (A)
Module Description Qty each Subtotal each Subtotal
FP0934 4100U-S1 Basic Panel 0.373 0.47
4100-1288 64/64 LED Switch Controller (1st controller per bay) 0.02 0.26
4100-1289 64/64 LED Switch Controller (2nd controller per bay) 0.02 0.26
4100-3101 IDNET module with 250 addressable devices 0.275 0.365
4100-0113 RS232 Modem Interface 0.13 0.13
4100-0154 VESDA HLI 0.13 0.13
4100-3003 8XSPDT,3A,24VDC Relay module 0.03 0.28
4100-3024 24 I/O Relay Motherboard + (4100-0302) 0.08 0.3
4100-4321 6 Supervised Relays 0.02 0.07
4100-5004 8 AZF Monitor Zone 0.08 0.2
4100-6014 Modular Network Card (Requires 2 media cards) 0.028 0.028
4100-6056 Wired Media Card RS485 0.055 0.055
4100-6057 Fibre Optic Media Card 0.025 0.025
4100-0160 Fire Panel Internet Interface Module 0.115 0.115
4100-0766 T-GEN 50 on Amplifier Bracket Voice (2 Slots) 0.05 2.2
4100-0895 MiniGen on Amplifier Bracket 0.00 0.9
4100-2895 2nd MiniGen on same Amplifier Bracket 0.00 0.9
2190-9156 ZAM Monitor - Mapnet 2 0.02 0.09
2190-9162 ZAM Signal - Mapnet 2 0.015 0.065
2190-9164 ZAM Control - Mapnet 2 0.01 0.04
4090-9101 Mapnet / IDNet Monitor ZAM 0.016 0.072
4090-
9117AU
Addressable IDNet Power Isolator 0.01 0.01
4090-
9120AU
IDNet 6 Point I/O Module (4 I/Ps + 2 relay O/Ps) 0.03 0.03
4090-9050 ZAM 4-20mA Analog - Mapnet 2 0.03 0.03
4098-9794E Sounder Base - TrueAlarm 0.015
4907-0012 Evac Tone Sounder - 24VDC 0.018
Other Loads
Other Loads
Total Power Supply Capacity I (S) = I(A) =