2-19
If more than 32 zones are required, a second controller (4100-1289) will be required.
Note that an ME0456 fan control module counts as 8 zones when adding up the controller
requirements.
LED 1. This LED illuminates if communication loss between the controller and the CPU
occurs. It is independent of jumper P1 (which configures different communication loss
features).
The 64/64 LED/switch controller requires physical configuration, but the LED/Switch
modules do not. Switch controller configuration consists of setting jumper P1 and setting
the card address. In the 4100U-S1, the first display controller is address 3 and the second
has address 4. Card addressing is covered in Appendix A.
Refer to the figure below to mount the display cards to the front of the expansion bay.
Figure 2-13. LED/Switch Card Mounting
Continued on next page
Step 6. Installing LED/Switch Modules into Expansion Bays, Continued
LED/Switch
Controller Card,
(continued)
Configuring the
LED/Switch
Controller Card
Mounting
LED/Switch Modules
to the Expansion
Bay
#6 UNC NUTS
GROUND
CONNECTION
ADDITIONAL
LED/SWITCH
CONTROLLER
GROUND
CONNECTION
LOCKWASHERS
LED/Switch Controller
assemblies are installed
in the end slot in the
basic 4100U-S1