Tyco 4100U-S1 Smoke Alarm User Manual


 
B-1
This appendix briefly summarises the programming that is required to comply with
AS4428.1.
It does not provide equations or detail of programming. Refer to LT0400 4100U-S1
Programming & Configuration Reference for descriptions of the AS 4428.1
programming. The separate 4100U Programming Manual tells how to use the PC-based
4100U Programmer.
The following is a list of functions that must be programmed under custom control.
Functionality must comply with AS4428.1, and be as described in the Operator’s Manual
LT0395.
Individual zone alarm indication, flashing until isolated, steady when isolated.
Common Zone Alarm indication, flashing when any zone in alarm is un-isolated,
steady when all zones in alarm are isolated.
Individual zone isolate pushbutton and indication.
Zone Alarm Test pushbutton and indication.
Zone Fault Test pushbutton and indication.
Warning System Isolate pushbutton and indication.
External Bells Isolate pushbutton and indication.
Ancillary Control Function and Isolate pushbutton and indication as required.
Weekly 1 hour battery test.
Fault indication after 8 hours of isolate.
The configuration templates for the 4100U-S1 all contain the necessary Custom Control
equations for these functions. These settings should not be altered except under advice
from Simplex.
The US options for power supply and AVF are selected, not the Canadian ones.
Features that do not comply with AS4428.1 must not be enabled, e.g. Alarm cut-out
times.
Features that are statutory in AS4428.1 must not be pass-code protected, e.g. zone
isolate, zone test (Fault and Alarm).
Appendix B
Programming Requirements
Introduction
Required Features
Notes