Tyco 4100U-S1 Smoke Alarm User Manual


 
3-14
The illustration below shows coupler wiring.
Figure 3-7. Coupler Wiring
Refer to the guidelines and figures in this topic to use wired media cards.
IMPORTANT: TB1 on the wired media card must not be used when it is
connected to the 4100-6014 NIC.
When the 4100-6056 (565-413) Interface Card is used with the 4100-6014
Network Card, TB1 on the Interface Card cannot be used. Network wiring must
be connected to the motherboard as shown.
The shield should only be connected at one end of the line. The shield is
connected to the left port.
Each cable requires two ferrite beads, one at each end. Refer to
Figure 5-1 for
bead wiring. Beads can be ordered as 4100-5129 (set of three).
When wiring leaves the building, 2081-9044 Overvoltage Protectors are
required. One overvoltage protector is installed where wiring leaves the
building; another is installed where wiring enters the next building.
Table 3-5. 566-227 CPU Motherboard Wired Media Connections
CPU Motherboard Port for
Media Card Connected to P5
Wired Media Card Connection
(Left Port)
TB1-4 0 V
TB1-5 Earth ground
TB1-6 INV (-)
TB1-7 None
TB1-8 NONINV (+)
CPU Motherboard Port for
Media Card Connected to P6
Wired Media Card Connection
(Right Port)
TB3-1 NONINV (+)
TB3-2 Reserved
TB3-3 INV (-)
TB3-4 Earth ground
TB3-5 0 V
Continued on next page
Step 4. Wiring Network Cards, Continued
4190-9010 Coupler
Requirements
(continued)
Wiring with the
Wired Media Card