Addressable cards include a bank of eight DIP switches. From left to right (see Figure A-
1, below) these switches are designated as SWx-1 through SWx-8. The function of these
switches is as follows:
SWx-1. This switch sets the data rate for the internal 4100U communications line
running between the card and the CPU. Set this switch to ON.
SWx-2 through SWx-8. These switches set the card’s address within the 4100U-
S1. Refer to Table A-1 for a complete list of the switch settings for all of the possible
card addresses.
Note: You must set these switches to the value assigned to the card by the 4100U
Programmer.
1
8
7
6
5
4
3
2
Figure A-1. DIP Switch SWx
Continued on next page
Appendix A
Card Address DIP Switch
Overview
ON
OFF
DIP Switches SWx-2 through
SWx-8 set the Card Address.
Figure shows an Address of 3.
4100 Comm. Baud Rate.
Switch (SWx-1)
Must Be Set to ON