Teledyne gfc 7000ta Carbon Monoxide Alarm User Manual


 
Getting Started Model GFC7000TA Carbon Dioxide Analyzer
Teledyne Analytical Instruments 23
3.5.4. Connecting the Status Outputs
If you wish utilize the analyzer’s status outputs to interface with a device that accepts logic-level digital
inputs, such as programmable logic controllers (PLC’s) they are accessed via a 12-pin connector on the
analyzer’s rear panel labeled STATUS.
STATUS
1 2 3 4 5 6 7 8 D
+
NOTE
Most PLC’s have internal provisions for limiting the current the input will draw.
When connecting to a unit that does not have this feature, external resistors must
be used to limit the current through the individual transistor outputs to 50mA
(120 Ω for 5V supply).
The pin assignments for the status outputs can be found in the table below:
Table 3-5: Status Output Pin-outs
OUTPUT #
STATUS
DEFINITION
CONDITION
1
SYSTEM OK
On if no faults are present.
2
CONC VALID
On if CO
2
concentration measurement is valid.
If the CO
2
concentration measurement is invalid, this bit is OFF.
3
HIGH RANGE
On if unit is in high range of DUAL or AUTO range modes.
4
ZERO CAL
On whenever the instruments ZERO point is being calibrated.
5
SPAN CAL
On whenever the instruments SPAN point is being calibrated.
6
DIAG MODE
On whenever the instrument is in DIAGNOSTIC mode.
7
ALARM1
On whenever the measured CO
2
concentration is above the set point for
ALM1
8
ALARM2
On whenever the measured CO
2
concentration is above the set point for
ALM2
D EMITTER BUS The emitters of the transistors on pins 1-8 are bused together.
+ DC POWER + 5 VDC
Digital Ground The ground level from the analyzer’s internal DC power supplies.