Napco Security Technologies GEM-P3200 Home Security System User Manual


 
L NAPCO Security Systems
X GEM-P3200 Programming Instructions
Page 55
WI818G 10/05
KEYPAD CONFIGURATION MODE
This section will focus on configuring the GEM-RP1CAe2/GEM-K1CA Keypads. If there is more than one keypad in the system, only
Keypad No. 1 may be used for programming.
KEYPAD INSTALLATION
Two types of keypads may be used with the GEM-P3200: the GEM-RP1CAe2/GEM-K1CA. Each must be assigned an address
number (1–7) and each requires its own configuration procedure (see CONFIGURING THE KEYPADS, which follows, and DIRECT
ADDRESS KEYPAD AREA OPTIONS). At least 1 keypad must be used; only 1 is required for a single-area Commercial Burglary
installation.
GEM-RP1CAe2/GEM-K1CA - is a 2-line combination fire/burglary/access keypad capable of supporting 4 EZM zones and a
PGM output.
The GEM-RP1CAe2 or GEM-K1CA is recommended for use as Keypad #1. See "Important Note" on page 2
for more information regarding the various buttons on the GEM-RP1CAe2/GEM-K1CA keypads.
CONFIGURING THE KEYPADS
A total of up to 7 keypads may be connected to the panel.
Configuring the GEM-RP1CAe2/GEM-K1CA Keypad
Each GEM-RP1CAe2/GEM-K1CA keypad must be configured for (a) keypad tactile beep; (b) entry sounder; (c) keypad address; (d)
compatibility number; (e) EZM address; and (f) zone response.
To enter the Keypad Configuration Mode:
1. Move jumper JP1 (located in the center of the control panel board) from Pins 1-2 (top two) to Pins 2-3 (bottom
two). NOTE: See Wiring Diagram on page 68.
2. After about 15 seconds, the display will read “XX OUT OF SYSTEM”, where XX indicates the keypad address.
3. Press
11123 R and proceed as follows. (Repeat the following procedure for
all keypads).
Keypad Tactile Beep
Upon entering the Keypad Configuration Mode, “KEYPAD BEEP ON” will be displayed,
indicating that the tactile beep, which sounds when any button is pressed, is on.
To turn off the tactile beep, press the U button (the U button will toggle the tac-
tile beep on and off).
Press R to continue or press C to exit.
Entry Sounder
To turn off the keypad entry sounder during entry time, press U (the U button
will toggle the entry sounder on and off).
Press R to continue or press
C to exit.
Keypad Address
If more than one keypad is installed, each must be assigned a unique keypad
address (that is, no two keypads may be numbered alike):
Keypads must be numbered consecutively (missing numbers are not permitted)
Only Keypad No. 1 may be used for programming.
To assign the keypad number, proceed as follows:
1. Enter the assigned keypad number 01–07, then press
U to save. A valid
number will be acknowledged by a short beep; an invalid number will be re-
jected by a long beep.
2. Press R to continue or press C to exit.
Keypad Beep
ON
NORMAL
KEYPAD
CONFIGURE
R
COMPUTERIZ ED SECURITY SYS TEM
GEMINI
A
R
M
E
D
S
T
A
T
U
S
SYSTEM ARMED
01/01/97 12:00AM
12
4
3
56
7890
A
B
C
D
E
F
G
NEXT/Y ES
PRIOR/NO
AREA
# OF ZONES IN AREA 1
ENTER # ZONES X X
# OF ZONES IN AREA
ENTER # ZONES XX
Entry Sounder
ON
Keypad Address
01