–65–
Note: 1 If there are any units which are not operating, it will cause refrigerant to accumulate, so by all means operate all the
indoor units. Also, in order to prevent stable operation from being disrupted by the thermostat going OFF, set the
trial operation mode.
Note: 2 If the high pressure is stabilized, it is safe to judge that the operation condition is stable.
Judge that operation is stabilized or not stabilized by whether the compressor starts after 3 or more minutes have
passed.
Note: 3 When turning on SW1 to
12345678910
ON
, the LED will display the liquid level.
Note: 4 If AL = 1, it indicates that adjustment is not necessary, but when the liquid level is on the low side even if it is in the
AL = 1 region, if one unit only is run and refrigerant is accumulating in the units that are stopped, it may result in
there being insufficient refrigerant, so at such a time, adjustment is necessary.
Note: 5 Determine the difference in the volume of refrigerant necessary for cooling and for heating as follows, and carry out
supplementary charging in accordance with the table below.
* The piping length is the total pipe length calculated for a high press pipe with a ø25.4 size.
If the liquid pipe size is ø 12.7, the actual length is 0.3
If the liquid pipe size is ø 9.52, the actual length is 0.2
If the liquid pipe size is ø 6.35, the actual length is 0.1
Pipe Length
Additional Refrigerant
Volume
60 m or less 60 ~ 90 m
90 m or longer
18 kg 27 kg 31 kg