–126–
Checking
code
7102
7105
7107
7111
7130
Meaning, detecting method Cause Checking method & Countermeasure
Connected unit count over
Address setting error
• Erroneous setting of OC unit
address
• Erroneous setting of BC con-
troller address
Trouble source :
Outdoor unit
BC controller
Branch No. setting error
Can not operate because branch
No. of indoor unit wrongly set.
Trouble source :
BC controller
Remote control sensor error
Error not providing the tempera-
ture designed to remote control-
ler sensor.
Trouble source :
Indoor unit
Different Indoor model and BC
controller connected error
2) The Outdoor unit address is being
set to 51~100 under automatic ad-
dress mode (Remote controller dis-
plays “HO”).
3) Disconnection of transmission wir-
ing at Outdoor unit.
4) Short circuit of transmission line in
case of 3) & 4), remote controller
displays “HO”.
5) Disconnection of transmission wir-
ing at BC controller.
6) BC controller not for the BIG R2
(model: FA, FB type) is connected.
1) Setting error of Outdoor unit ad-
dress.
The address of Outdoor unit is not
being set to 51~100.
2) The address of BC controller is not
being set within 51~100.
1) Indoor unit capacity per connector
joint is exceeded as follows:
Single connection :
81 or more
Two connection joint :
161 or more
Three connection joint :
241 or more
Four connection joint :
321 or more
2) Four or more indoor units are set
for the same connection.
3) The smallest branch No. has not
been set when used at joint.
4) Does the address of BC controller
(slave) become the least address +
50 of Indoor controller connecting
to BC controller (slave)?
5) The address of Indoor Unit, which
is connected to BC controller
(slave), sets up the small address
from the greatest address of Indoor
Unit which is connected to BC con-
trol (master).
1) In case when the old type remote
controller for M-NET is used and the
remote controller sensor is de-
signed on indoor unit. (SW1-1
turned ON)
A indoor unit not for the R407C (model:
P•••) is connected.
d) Check for the model total (capacity code total)
of indoor units connected.
Check that the address of OC unit is being set to
51~100.
Reset the address if it stays out of the range, while
shutting the power source off.
When BC controller is out of the range, reset it while
shutting the power source of both OC unit and BC
controller off.
a) Check indoor unit connection No. in refrigerant
circuit.
1 No four or more indoor units which are set
for the same branch No. A?
2 Check total capacity of indoor units which
are set for the same branch No. Judged as
trouble when it applies to Cause 1).
3 Check whether the smallest branch No. is
set when used at joint.
b) Check whether indoor unit capacity code (SW2)
is wrongly set. (Keep factory shipment condition.)
For erroneous switch setting, modify it, turn off
the power source of outdoor unit, and indoor unit
simultaneously for 5 minutes or more, and then
turn on.
C) Verify the address of BC controller (slave) and
Indoor Unit.
a) Replace the old remote controller by the new
remote controller.
Use the P••• indoor unit.