Mitsubishi Electronics PURY-P400 Air Conditioner User Manual


 
49
Mode
Connection
[2] Control of BC Controller
(1) Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Cooling Heating Stop Defrost
SVA ON OFF OFF OFF
SVB OFF ON OFF OFF
SVC ON OFF OFF OFF
(2) Control of SVM1 (only FA type)
SVM1 is turned on and off corresponding to operation mode.
Operation mode Cooling-only Cooling-main Heating-only Heating-main Stop
SVM1 ON OFF OFF OFF OFF
* Please confirm that the above parts of BC controllers are being color-corded and shown with the name plate inside
the BC controller unit.
(3) Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows: (Number of pulse)
*1
*2
*3
Superheat
control
Differential
pressure control
Control every minute so that superheat amount detected by bypass inlet and oulet
temperatures TH12, TH15 stay in the specified range.
(FA: TH12, TH15, FB: TH22, TH25)
Control every minute so that detected differential pressure (PS1, PS3) stay in the
specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
Operation mode
2000
Superheat
control *1
60
Differential
Pressure control
*2
60
2000
60
60
LEV1
LEV3
LEV3a
Liquid level
control *3
Differential
pressure control
*2
60
Differential
Pressure control
*2
Cooling-only Heating-only Cooling-main Heating-main Stop
FA
FB
Superheat
control *1
Superheat
control *1
Superheat
control *1