Mitsubishi Electronics PURY-P400 Air Conditioner User Manual


 
118
(2) Communication/system
Checking
code
6600
6602
Multiple address error
Transmission from units with the
same address is detected.
Note:
The address/attribute
shown on remote
controller indicates the
controller which has
detected error.
Transmission processor hardware
error
Though transmission processor
intends to transmit 0, 1 is dis-
played on transmission line.
Note:
The address/attribute
shown on remote
controller indicates the
controller which has
detected error.
Meaning, detecting method Cause Checking method & Countermeasure
At the genration of 6600 error, release the error by
remote controller (with stop key) and start again.
a) If the error occures again within 5 minutes.
Search for the unit which has the same address
with that of the source of the trouble.
When the same address is found, turn off
the power source of outdoor unit, BC con-
troller, and indoor unit for 5 minutes or more
after modifying the address, and then turn
on it again.
b) When no trouble is generated even continuing
operation over 5 minutes.
The transmission wave shape/noise on the
transmission line should be investigated in ac-
cordance with <Investigation method of trans-
mission wave shape/noise>.
1) Two or more controllers of outdoor
unit, indoor unit, remote controller,
BC controller, etc. have the same
address.
2) In the case that signal has changed
due to noise entered into the trans-
mission signal.
1) At the collision of mutual transmission data generated during the wiring work or polarity
change of the transmission line of indoor or outdoor unit while turning the power source
on, the wave shape is changed and the error is detected.
2) 100V power source connection to indoor unit or BC controller.
3) Ground fault of transmission line.
4) Insertion of power supply connector (CN40) of plural outdoor units at the grouping of
plural refrigerant systems.
5) Insertion of power supply connector (CN40) of plural outdoor units in the connection
system with MELANS.
6) Faulty controller of unit in trouble.
7) Change of transmission data due to the noise in transmission.
8) Connection system with plural refrigerant systems or MELANS for which voltage is not
applied on the transmission line for central control.