Honeywell THX9321 Thermostat User Manual


 
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ 2.0 WITH EIM
68-0311—01 36
6080 Dirty Filter Alert Dry
Contact Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed:
Normally Open: The Dry Contact device is normally
open and will close when the device detects a dirty
filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a dirty filter.
6090 What Terminals are
Wired to the Water
Leak Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
6100 Water Leak Alert Dry
Contact Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed:
Normally Open: The Dry Contact device is normally
open and will close when the device detects water.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects water.
6110 What Terminals are
Wired to the System
Shutdown Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
6120 System Shutdown
Alert Dry Contact
Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed:
Normally Open: The Dry Contact device is normally
open and will close when the device is activated.
Normally Closed: The Dry Contact device is
normally closed and will open when the device is
activated.
6130 What Terminals are
Wired to the Service
Needed Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
6140 Service Needed Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed:
Normally Open: The Dry Contact device is normally
open and will close when the device is activated.
Normally Closed: The Dry Contact device is
normally closed and will open when the device is
activated.
6150 What Terminals are
Wired to the Fan
Failure Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number Installer Setup Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes