Honeywell THX9321 Thermostat User Manual


 
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ 2.0 WITH EIM
35 68-0311—01
6020 Remote Setback Dry
Contact Setup
Normally Open when Occupied
Normally Closed when Occupied
Normally Open
when Occupied
Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed:
Normally Open when Occupied: The Dry Contact
device is open when the room is occupied and will
close when the room is unoccupied.
Normally Closed when Occupied: The Dry Contact
device is closed when the room is occupied and will
open when the room is unoccupied.
6030 Remote Setback Time
Delay from Occupied
to Unoccupied
0 to 30 minutes (in 5 minute
increments)
0 minutes Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
The Remote Setback Time Delay forces the
thermostat to wait before it switches from Occupied
to Standby temperature settings.
When set to 0 minutes, the thermostat will switch
from Occupied to Standby temperature settings
immediately when the room is unoccupied.
6040 Remote Setback -
Standby Cool
Setpoint
72° F to 90° F 85° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to STANDBY (setback
settings) when no one is in the room. If someone is
in the room, then it follows the settings of the
occupied period. The occupancy sensor is ignored
during unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
STANDBY settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.
6040 Remote Setback -
Standby Heat
Setpoint
50° F to 70° F 64° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to STANDBY (setback
settings) when no one is in the room. If someone is
in the room, then it follows the settings of the
occupied period. The occupancy sensor is ignored
during unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
STANDBY settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.
6050 What Terminals are
Wired to the Full
Drain Pan Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
6060 Full Drain Pan Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of device
installed.
Normally Open: The Dry Contact device is normally
open and will close when the device detects the
drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects the drain pan is full.
6070 What Terminals are
Wired to the Dirty
Filter Alert Dry
Contact?
None
S1
S2
None Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number Installer Setup Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes