Bryant 580J*04--12 Air Conditioner User Manual


 
6
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water
Rinse
A periodic clean water rinse is very beneficial for coils
that are applied in coastal or industrial environments.
However, it is very important that the water rinse is made
with a very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
Routine Cleaning of Coil
Surfaces
Periodic cleaning with TotalineR environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Bryant Replacement
Components Division as part number P902--0301 for a one
gallon container, and part numbe r P902--0305 for a 5
gallon container. It is recommended that all coils,
including standard aluminum, pre--coated, copper/copper
or E--coated coils be cleaned with the Totaline
environmentally sound coil cleaner as described below.
Coil cleaning should be part of the unit’s regularly
scheduled maintenance procedures to ensure long life of
the coil. Failure to clean the coils may result in reduced
durability in the environment.
Avoi d use of:
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Totaline environmentally sound coil cleaner is
nonflammable, hypo allergenic, non bacterial, and a
USDA accepted biodegradable agent that will not harm
the coil or surrounding components such as electrical
wiring, painted metal surfaces, or insulation. Use of
non--recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
One--Row Coil
Wash coil with commercial coil cleaner. It is not
necessary to remove top panel.
Two--Row Coils
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 8. To
hold top panel open, pl ace coil corner post betwee n
top panel and center post. See Fig. 9.
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fastener holding coil sections together at re-
turn end of condenser coil. Careful ly sepa rate the out-
er coil section 3 to 4 in. from the inner coil section.
See Fig. 10.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
7. Secure inner and outer coil rows together with a
field-- supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
C08205
Fig. 8 -- Cleaning Condenser Coil
C08206
Fig. 9 -- Propping Up Top Panel
C08207
Fig. 10 -- Separating Coil Sections
Totaline Environmentally Sound Coil Cleaner
Application E quipment
S 2--1/2 gallon garden sprayer
S Water rinse with low velocity spray nozzle
580J