Table 1 – Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Condenser
Fan Will Not Start.
Power failure. Call power company.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Replace component.
Insufficient line voltage. Determine cause and correct.
Incorrect or f a ulty wiring. Check wiring diagram and rewire correctly.
Thermostat setting too high. Lower t hermostat setting below room temperature.
Compressor Will Not Start But
Condenser Fan Runs.
Faulty wiring or loose connections in compres-
sor circuit.
Check wiring and repair or replace.
Compressor m otor burned out, seized, o r
internal overload open.
Determine cause. Replace compressor.
Defective run/start capacitor, overload, start
relay.
Determine cause and replace.
Onelegofthree---phasepowerdead.
Replace fuse or reset circuit breaker. Determine
cause.
Compressor Cy cle s (other
than normally satisfying
thermostat).
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, an d recharge
to nameplate.
Defective compressor. Replace and determine cause.
Insufficient line voltage. Determine cause and correct.
Blocked condenser. Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Determine cause and replace.
Defective thermostat. Replace t hermostat.
Faulty condenser---fan m otor or capacitor. Replace.
Restriction in refrigerant system. Locate restriction and remove.
Compressor Operates
Continuously.
Dirty air filter. Replace filter.
Unit undersized for load. Decrease load or increase unit size.
Thermostat set too low. Reset thermostat.
Low refrigerant charge. Locate leak; repair and recharge.
Leaking valves in compressor. Replace compressor.
Air in system. Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted. Clean coil or remove restriction.
Excessive Head Pressure.
Dirty air filter. Replace filter.
Dirty condenser coil. Clean coil.
Refrigerant overcharged. Recover excess refrigerant.
Air in system. Recover refrigerant, evacuate system, and recharge.
Conden ser air restricted or air short---cycling. Determine cause and correct.
Head Pressure Too Low.
Low refrigerant charge. Check for leaks; repair and recharge.
Compressor valves leaking. Replace compressor.
Restrictioninliquidtube. Remove restriction.
Excessive Suction Pressure.
High head load. Check for source and eliminate.
Compressor valves leaking. Replace compressor.
Refrigerant overcharged. Recover excess refrigerant.
Suction Pressure Too Low.
Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks; repair and recharge.
Metering device or low side restricted. Remove source of restriction.
Insufficient evaporator airflow.
Increase air quantity. Check f ilter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Outdoor ambient below 25˚F. Install low---ambient kit.
Evaporator Fan Will Not
Shut Off.
Time off delay not finished. Wait f or 30 --- second off delay.
Compressor Makes Excessive
Noise.
Compressor rotating in wrong direction. Reversethe3---phasepowerleads.
580J