Bryant 580J*04--12 Air Conditioner User Manual


 
31
Table 11 (cont.) -- Altitude Compensation* (A08--A12)
ELEVATION
ft (m)
125,000
BTUH Nominal
250,000
BTUH Nominal
180,000, 224,000
BTUH Nominal
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
0 --- 2000 (610) 31
1
49
3
†30 46
3
31
1
48
3
2000 (610) 32
1
50
3
†30 47
3
32
1
49
3
3000 (914) 32
1
50
3
31
1
47
3
32
1
49
3
4000 (1219) 33
1
50
3
31
1
48
3
33
1
49
3
5000 (1524) 33
1
51
4
31
1
48
3
33
1
50
3
6000 (1829) 34
1
51
4
31
1
48
3
34
1
50
3
7000 (2134) 35
1
51
4
32
1
49
3
35
1
50
3
8000 (2438) 36
1
52
4
33
1
49
3
36
1
51
4
9000 (2743) 37
2
52
4
34
1
50
3
37
2
51
4
10000 (3048) 38
2
52
4
35
1
50
3
38
2
52
4
11000 (3353) 39
2
53
4
36
1
51
4
39
2
52
4
12000 (3658) †41 53
4
37
2
51
4
†41 53
4
13000 (3962) †42 54
4
38
2
52
4
†42 53
4
14000 (4267) †43 54
4
†40 53
4
†43 54
4
Table 12 – Altitude Compensation* (04--06) -- Low NO
x
Units
ELEVATION
ft (m)
60,000, 90,000
BTUH Nominal
120,000
BTUH Nominal
NG Orifice Size LP Orifice Size NG Orifice Size LP Orifice Size
0 --- 2000 (610) 38
2
53
4
32
1
50
3
2000 (610) 39
2
54
4
33
1
51
4
3000 (914) †40 54
4
34
1
51
4
4000 (1219) †41 54
4
35
1
51
4
5000 (1524) †41 54
4
35
1
51
4
6000 (1829) †42 54
4
36
1
52
4
7000 (2134) †42 54
4
36
1
52
4
8000 (2438) †43 55
4
37
2
52
4
9000 (2743) †43 55
4
38
2
53
4
10000 (3048) 44
2
55
4
†40 53
4
11000 (3353) 44
2
55
4
†41 53
4
12000 (3658) 45
2
†56 †42 54
4
13000 (3962) 47
3
†56 †43 54
4
14000 (4267) 48
3
†56 †43 55
4
LEGEND:
NG = Natural Gas LP = Liquid Propane 1 = CRLPELEV001A00
* As the height above sea level increases, there is less oxygen per cubic
ft.ofair.Therefore,heatinputrateshouldbereducedathigheraltitudes.
2 = CRLPELEV002A00
3 = CRLPELEV003A00
{ Not incl uded in kit. M ay be purchased separately through dealer. 4 = CRLPELEV004A00
Minimum heating entering air temperature
When operating on first stage heating, the minimum
temperature of air entering the dimpled heat exchanger is
50_F continuous and 45_F intermittent for standard heat
exchangers and 40_F continuous and 35_F intermittent for
stainless steel heat exchangers. To operate at lower
mixed--air temperatures, a fie ld--supplied outdoor --air
thermostat must be used to initiate both stages of heat
when the temperature is below the minimum required
temperature to ensure full fire operation. Wire the
outdoor--air thermostat (part no. HH22AG106) in series
with the sec ond stage gas valve as shown below. Set the
outdoor--air thermostat at 35_F for stainless steel heat
excha ngers or 45_F for standard heat exchangers. This
temperature setting will bring on the second stage of heat
whenever the ambient temperature is below the thermostat
setpoint. Indoor comfort may be compromised when
heating is initiated using low entering air temperatures
with insufficient heating temperature rise.
LCTB
W2
Thermostat
TH1
TH2
W1
W1
W2
OALT
C08442
Troubleshooting Heating System
Refer to Table 13 and Table 14 for additional
troubleshooting topics.
580J