APPENDIX II. PHYSICAL DATA (cont.)
Physical Data (Heating) 3 -- 6 TONS
580J*04 580J*05 580J*06 580J*07
Gas Connection
#ofGasValves 1 1 1 1
Connection size 1/2” NPT 1/2” NPT 1/2” NPT 1/2” NPT
Nat. gas supply li ne press (in. w.g.)/(PSIG) 5 --- 13 / 0.18 --- 0.47 5 --- 13 / 0.18 --- 0.47 5 --- 13 / 0.18 --- 0.47 5 --- 13 / 0.18 --- 0.47
LP supply line press (in. w.g.)/(PSIG) 11---13 / 0.40---0.47 11---13 / 0.40---0.47 11---13 / 0.40---0.47 11---13 / 0.40---0.47
Heat Anticipator Setting (Amps)
1st s tage 0.14 0.14 0.14 0.14
2nd stage 0.14 0.14 0.14 0.14
Natural Gas Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise 25 / 55 25 --- 55 25 --- 55 25 --- 55
MED
#ofstages/#ofburners(total) 1or2/3 1/3 1/3 1/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise 55 / 85 35 / 65 35 / 65 35 / 65
HIGH
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
Temperature rise --- 50 / 80 50 / 8 0 50 / 80
Liquid Propane Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 1/2
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise 25 / 55 25 --- 55 25 --- 55 25 --- 55
MED
#ofstages/#ofburners(total) 1or2/3 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 195 / 115
Temperature rise 55 / 85 35 / 65 35 / 65 35 / 65
HIGH
#ofstages/#ofburners(total) --- 1or2/3 1or2/3 1or2/3
Rollout switch opens / Closes --- 195 / 115 195 / 115 195 / 115
Temperature rise --- 50 / 80 50 / 8 0 50 / 80
Low NO
x
Gas Heat
LOW
#ofstages/#ofburners(total) 1/2 1/2 1/2 ---
Rollout switch opens / Closes 195 / 115 195 / 115 195 / 115 ---
Temperature rise 20 / 50 20 / 50 20 / 50 ---
MED
#ofstages/#ofburners(total) 1/3 1/3 1/3 ---
Rollout switch opens / closes 195 / 115 195 / 115 195 / 115 ---
Temperature rise 30 / 60 30 / 60 30 / 60 ---
HIGH
#ofstages/#ofburners(total) --- 1/3 1/3 ---
Rollout switch opens / Closes --- 195 / 115 195 / 115 ---
Temperature rise --- 40 / 70 40 / 7 0 ---