Bryant 580G Air Conditioner User Manual


 
UNIT SIZE
580H
OPERATING
WEIGHT
AB
CORNER WEIGHT
(lb)
lb ft-in. ft-in. 1 2 3 4
240 350 4176 6- 0
3
8
3-6
3
8
879 954 1220 1124
240 525 4256 6- 1
5
16
3-6
11
16
917 973 1218 1148
300 350 4262 5- 9
5
8
3-8 899 899 1232 1232
300 525 4342 5-10
1
8
3-8
5
16
929 916 1240 1257
324 525 4262 5- 9
5
8
3-8 899 899 1232 1232
324 525 4342 5-10
1
8
3-8
5
16
929 916 1240 1257
360 350 4262 5- 9
5
8
3-8 899 899 1232 1232
360 525 4342 5-10
1
8
3-8
5
16
929 916 1240 1257
Fig. 3 Base Unit Dimensions, 580H240-360
NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue discharge facing
economizer inlet. Min. clearances to be:
Adjacent Units: 15Ј-0Љ
Top of Units: No Overhang
Condenser Coil: 4Ј-0Љ
Economizer Side: 6Ј-0Љ
Heat Side: 4Ј-0Љ
Filter Access Side: 10Ј-0Љ (For Removal of Evapora-
tor Coil)
4. For smaller service and operational clearances, con-
tact Application Engineering department.
5. Dimensions are in inches.
6. For side supply/return applications a single return and
supply ductwork connection is recommended for cov-
ering both return and both supply openings.
—4—