Bryant 580G Air Conditioner User Manual


 
Table 3— Electrical Data 580G,H240-360
UNIT
SIZE
580G,H
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
COMBUSTION
FAN MOTOR
POWER SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp
FLA
(ea)
Hp FLA FLA LRA FLA MCA MOCP*
240
208/230 187 254 39.1 228 25.6 160 2 1 5.3
5
16.7/
15.2
0.96 101.8/100.3 125/125
23.6 41.6 0.96 125.4/123.9 150/150
10
30.8/
28.0
0.96 115.9/113.1 150/150
23.6 41.6 0.96 139.5/136.7 175/175
15
46.2/
42.0
0.96 131.3/127.1 150/150
23.6 41.6 0.96 154.9/150.7 175/175
460 414 508 19.9 114 11.5 80 2 1 2.7
5 7.6
0.50 49.4 60
12.6 23.6 0.50 62.0 80
10 14.0
0.50 55.8 70
12.6 23.6 0.50 68.4 80
15 21.0
0.50 62.8 80
12.6 23.6 0.50 75.4 90
575 518 632 16.0 91 9.6 64 2 1 2.4
5 6.1
0.50 40.5 50
12.6 23.6 0.50 53.1 60
10 11.0
0.50 45.4 60
12.6 23.6 0.50 58.0 70
15 17.0
0.50 51.4 60
12.6 23.6 0.50 64.0 80
300
208/230 187 254 39.1 228 39.1 228 2 1 5.3
7.5
24.2/
22.0
0.96 122.8/120.6 150/150
23.6 41.6 0.96 146.4/144.2 175/175
10
30.8/
28.0
0.96 129.4/126.6 150/150
23.6 41.6 0.96 153.0/150.2 175/175
15
46.2/
42.0
0.96 144.8/140.6 175/175
23.6 41.6 0.96 168.4/164.0 200/200
460 414 508 19.9 114 19.9 114 2 1 2.7
7.5 11.0
0.50 61.2 80
12.6 23.6 0.50 73.8 90
10 14.0
0.50 64.2 80
12.6 23.6 0.50 76.8 90
15 21.0
0.50 71.2 90
12.6 23.6 0.50 83.8 100
575 518 632 16.0 91 16.0 91 2 1 2.4
7.5 9.0
0.50 49.8 60
12.6 23.6 0.50 62.4 70
10 11.0
0.50 51.8 60
12.6 23.6 0.50 64.4 80
15 17.0
0.50 57.8 70
12.6 23.6 0.50 70.4 80
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Fuse or HACR circuit breaker.
or
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where aphase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452=5v
(BC) 464 − 457=7v
(AC) 457 − 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
—12—