12.6.3 Address Settings
The DX4020 has specific DIP switch settings for SDI
Address 88 when using the DX4020 for Remote
Programming Software (RPS) or enhanced
communications in a LAN or WAN environment.
Refer to Figure 28 for the correct switch settings.
Figure 28: DX4020 DIP Switch Settings
R
Y
G
B
1
2
=
3
=
=
Switch is not used
OPEN
123456
78
4
1 - DIP Switches
2 - ON position
3 - OFF position
4 - SDE Address 88 switch settings
Place a jumper over Pin 8 for the D9133TTL-E (SDI
Address 88) to be used for RPS or enhanced
communications in a LAN or WAN environment.
Figure 29: D9133TTL-E Jumper Setting for
Address 88
1234
88
12.6.4 Supervision
Supervision of the D9133DC, D9133TTL-E, and
D9133TTL-TR at SDI Address 88 is available through
programming that ensures operation between the
module and the control panel.
If supervised and the module does not respond to
control panel supervision polls, SERVC SDI 88
appears at the keypad. The report to the receiver
includes the address of the troubled module indicating
which module needs service.