Intelli-Start will only work on a Constant Volume
system using a space sensor.
Intelli-Start will only work when the internal
scheduling feature is used. It will not work using
a hard wired or communicated Occupied com-
mand.
Intelli-Start will only function during the fi rst
occupied period of each day.
Sequence of Operation
First day of heating or cooling operation
Two hours prior to the start of the occupied period
the Simplicity Control will compare the space
temperature to the “CV OCCUPIED COOLING”
or the “CV OCCUPIED HEATING” set points.
Heating operation
If the space temperature is 1.5° F or more
below the “CV OCCUPIED HEATING” set
point the Simplicity Elite control will stage on
the heat using the normal heating with space
sensor logic.
– The Simplicity Elite control will record the
space temperature and how long it takes to
bring the space temperature to the “CV OC-
CUPIED HEATING” set point.
– When the “CV OCCUPIED HEATING” set
point is reached the Simplicity Elite control
will divide the elapsed time into 5-minute
increments.
The Simplicity Elite control will determine
how many 0.1° F the temperature was below
the “CV OCCUPIED HEATING” set point.
The Simplicity Elite control will then cal-
culate how many 0.1° F were satisfi ed per
5-minute increment.
This number will be recalculated each day.
The Simplicity Elite control also records the
outdoor temperature when the above calcula-
tions are made.
Cooling operation
If the space temperature is 1.5° F or more
above the “CV OCCUPIED COOLING” set
point the Simplicity Elite control will stage on
cooling operation using the normal Cooling
with space sensor logic.
– The Simplicity Elite control will record the
space temperature and how long it takes to
bring the space temperature to the “CV OC-
CUPIED COOLING” set point.
– When the “CV OCCUPIED COO0LING” set
point is reached the Simplicity Elite control
will divide the elapsed time into 5-minute
increments.
The Simplicity Elite control will determine
how many 0.1° F the temperature was above
the “CV OCCUPIED COOLING” set point
The Simplicity Elite control will then cal-
culate how many 0.1° F were satisfi ed per
5-minute increment.
This number will be recalculated each day.
The Simplicity Elite control also records the
outdoor temperature when the above calcula-
tions are made.
Subsequent Operation
Each morning two hours before the scheduled
occupied start time the Simplicity Elite control
looks at the space temperature and the “CV OC-
CUPIED COOLING” and “CV OCCUPIED
HEATING” set points and determines if there is
a need for cooling or heating operation.
Based on which need is identifi ed the Simplicity
Elite control will calculate the number of 0.1°
F increments the space temperature is from set
point and multiple this value time the previous
days calculation on the number of 0.1° F the unit
can satisfy in 5 minutes. This will determine
how many minutes prior to the beginning of the
occupied period the control will need to start the
heating or cooling operation.
If cooling mode is selected the Simplicity Elite
control will also compare the current outdoor
temperature to the outdoor temperature recorded
during the previous days start up period.
If the current outdoor air temperature is
10.0° F or more above the previous day the
Simplicity Elite control will add 5 minutes to
the above calculated recovery time for every
10.0° F difference.