York YPAL 050 Air Conditioner User Manual


 
147
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
7
TABLE 7-1 – DEFINITIONS (CONTINUED)
Continued on next page
MENU ITEM DEFINITION
HSP1
THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH
PRESSURE SWITCH FOR COMPRESSOR SYSTEM 1 TO THE
UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.
HSP2
THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH
PRESSURE SWITCH FOR COMPRESSOR SYSTEM 2 TO THE
UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.
HSP3
THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH
PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE
UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.
HSP4
THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH
PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE
UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.
HYDRONIC HEAT ACTUATOR VALVE REVERSE
ACTING
THIS PARAMETER REVERSES THE ACTION OF THE HYDRONIC
VALVE. WHEN THE PARAMETER IS TURNED ON A 2 VOLT INPUT
TO THE VALVE IS FULL OPEN AND A 10 VOLT INPUT TO THE
VALVE IS FULL CLOSED
HYDRONIC HEATING ENABLED
THIS PARAMETER MUST BE TURNED ON TO ENABLE HYDRONIC
HEATING OPERATION
HYDRONIC HEATING STAGE #1 SUPPLY AIR
SETPOINT
THIS PARAMETER ESTABLISHES THE SETPOINT FOR
CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING
FIRST STAGE OPERATION
HYDRONIC HEATING STAGE #2 SUPPLY AIR
SETPOINT
THIS PARAMETER ESTABLISHES THE SETPOINT FOR
CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING
SECOND STAGE OPERATION AND ALSO THE CONTROL
SETPOINT FOR VAV HYDRONIC HEATING OPERATION
IAQ SENSOR RANGE
THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THE
RANGE OF THE CO2 SENSOR IN PPM
IAQ SETPOINT
THE UNIT CONTROLLER WILL TRY AND MAINTAIN THE CO2
LEVEL IN THE SPACE TO WITHIN +/- 100 PPM OF THIS VALUE
INDOOR FAN (G)
THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL G
- SUPPLY FAN
INDOOR FAN MIN RUN TIME
THIS GIVES THE STATUS OF THE MINIMUM SUPPLY FAN RUN
TIME IN SECONDS
INDOOR FAN OUTPUT
THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE
UNIT CONTROLLER TO THE SUPPLY FAN
INDOOR FAN VFD OUTPUT
THIS GIVES THE STATUS OF THE ANALOG OUTPUT FROM THE
UNIT CONTROLLER TO THE SUPPLY FAN IN %
INPUT AIR PROVING SWITCH
THIS IS THE STATUS OF THE AIR PROVING SWITCH INPUT TO
THE UNIT CONTROLLER, OFF OR ON
INPUT DIRTY FILTER SWITCH
THIS IS THE STATUS OF THE DIRTY FILTER SWITCH INPUT TO
THE UNIT CONTROLLER, OFF - CLEAN FILTER, ON - DIRTY
FILTER
INPUT INDOOR FAN OVERLOAD SWITCH
THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE
SUPPLY FAN OVERLOAD TO THE UNIT CONTROLLER, OFF -
FAULT, ON - NORMAL OPERATION