139
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
Continued on next page
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
C6 H 198 H - - - ASCD TIMER FOR COMPRESSOR #4 HIGH BYTE
C6 L 198 L - - -
ASCD TIMER FOR COMPRESSOR #4 LOW BYTE (SECONDS,
COUNTS DOWN)
C7 H 199 H 0 - -
COMPRESSOR #1 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C7 L 199 L 0 - -
COMPRESSOR #1 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
C8 H 200 H 0 - -
COMPRESSOR #2 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C8 L 200 L 0 - -
COMPRESSOR #2 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
C9 H 201 H 0 - -
COMPRESSOR #3 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C9 L 201 L 0 - -
COMPRESSOR #3 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
CA H 202 H 0 - -
COMPRESSOR #4 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
CA L 202 L 0 - -
COMPRESSOR #4 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
CB H 203 H - - - FAN ASCD TIMER HIGH BYTE (ALWAYS ZERO)
CB L 203 L - - - FAN ASCD TIMER LOW BYTE. (SECONDS, COUNTS DOWN)
CC H 204 H 0 - - FAN MINIMUM RUN TIMER (SECONDS, COUNTS DOWN)
CD H 205 H 0 - - FAN ON DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)
CD L 205 L 0 - - FAN OFF DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)
CE H 206 H 0 - - FAN ON DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)
CE L 206 L 0 - - FAN OFF DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)
CF H 207 H 0 0 255
ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, HIGH
BYTE)
CF L 207 L 0 0 255
ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, LOW
BYTE)
D4 H 212 H - 0 100 SUPPLY FAN VFD OUTPUT STATUS, 0-100% (2 – 10 VDC)
D4 L 212 L - 0 100 EXHAUST DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)
D5 H 213 H - 0 100 HOT WATER VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)
D5 L 213 L - 0 100 HOT GAS REHEAT VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)
D6 H 214 H - 0 100 ECONOMIZER DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)
D7 H 215 H NA 0 - - OPTION BYTE #6
0 1 = COMFORT VENTILATION FOR COOLING ENABLED
1 1 = COMFORT VENTILATION FOR HEATING ENABLED
2 1 = TEMPERATURE / HUMIDITY CONTROL ENABLED
3 1 = HOT GAS REHEAT ALTERNATE OPERATION ENABLED
4 1 = NETWORK OCCUPIED FLAG: OCC IS ON
5NA
6 1 = DIFFERENTIAL ENTHALPY MODE ENABLED
7NA