User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
Continued on next page
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
3 1 = ADDRESS / DOWN BUTTON PRESSED
4NA
5NA
6NA
7NA
18 H 24 H NA - - - OUTPUT STATUS BYTE #1
0 1 = COMPRESSOR #1 ON
1 1 = COMPRESSOR #2 ON
2 1 = COMPRESSOR #3 ON
3 1 = COMPRESSOR #4 ON
4 1 = CONDENSER FAN #1 ON
5 1 = CONDENSER FAN #2 ON
6 1 = INDOOR FAN ON
7 1 = EXHAUST FAN ON
18 L 24 L NA - - - OUTPUT STATUS BYTE #2
0 1 = STAGE 1 HEAT ON
1 1 = STAGE 2 HEAT ON
2 1 = STAGE 3 HEAT ON
3NA
4NA
5NA
6NA
7NA
19 H 25 H NA - - - OUTPUT STATUS BYTE #3
0 1 = COMPRESSORS OFF BECAUSE FREE COOLING IS AVAILABLE
1 1 = COMPRESSORS OFF BECAUSE OF LOW AMBIENT
2 1 = COMPRESSORS OFF BECAUSE SUPPLY VOLTAGE IS LOW
3 1 = CONTROL IS IN COMFORT VENTILATION MODE
4 1 = DISABLE CONTROL IS ACTIVE
5 1 = ECONOMIZER IS USING FREE COOLING
6NA
7NA
19 L 25 L NA - - - OUTPUT STATUS BYTE #4
0 1 = COMPRESSOR #1 OFF BECAUSE OF ASCD
1 1 = COMPRESSOR #2 OFF BECAUSE OF ASCD
2 1 = COMPRESSOR #3 OFF BECAUSE OF ASCD
3 1 = COMPRESSOR #4 OFF BECAUSE OF ASCD
4NA
5NA
6NA
7NA
1A H 26 H NA 12 - - OPTION BYTE #2