York YPAL 050 Air Conditioner User Manual


 
137
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
Continued on next page
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
A4 H 164 H - 0 255
SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,
HIGH BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)
A4 L 164 L - 0 255
SPACE SENSOR TEMPERATURE (ROOM AIR) (1/10 DEGREES,
LOW BYTE, 16 BIT VALUE, 0 = -40 DEGREES F)
A5 L 165 L 3 0 5 SPACE SENSOR OFFSET RANGE (DEGREES)
A6 L 166 L - 0 100 RETURN AIR HUMIDITY (%)
A7 L 167 L - 0 100 OUTSIDE AIR HUMIDITY (%)
A8 H 168 H - 0 255 DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, HIGH BYTE)
A8 L 168 L - 0 255 DEMAND VENTILATION (IAQ) VALUE (PPM VALUE, LOW BYTE)
A9 H 169 H - 0 255
BUILDING PRESSURE VALUE (0.001” WC, HIGH BYTE, 0 = -0.250”
WC, MAX = 0.250” WC)
A9 L 169 L - 0 255
BUILDING PRESSURE VALUE (0.001” WC, LOW BYTE, 0 = -0.250”
WC, MAX = 0.250” WC)
AA H 170 H - 0 255
DUCT PRESSURE VALUE (0.01” WC, HIGH BYTE, 0 = 0.00” WC,
MAX = 5.00” WC)
AA L 170 L - 0 255
DUCT PRESSURE VALUE (0.01” WC, LOW BYTE, 0 = 0.00” WC, MAX
= 5.00” WC)
AB H 171 H 0 0 200
REMOTE CONTROL INPUT VALUE (0.05 VDC COUNTS FOR
COOLING SAT SETPOINT SCALING)
AB L 171 L 40 0 200
DEMAND VENTILATION SETPOINT (25 PPM INCREMENTS,
MAXIMUM 5000 PPM)
AC L 172 L 80 0 200
AIR QUALITY (DV) SENSOR RANGE (25 PPM INCREMENTS,
MAXIMUM 5000 PPM)
AD L 173 L 60 0 240 UNOCCUPIED OVERRIDE TIME PERIOD (MINUTES)
AE H 174 H 45 0 100
OUTDOOR AIR TEMPERATURE COOLING LOCKOUT
TEMPERATURE (DEGREES F, 0 = DISABLED)
AE L 174 L 75 0 100
OUTDOOR AIR TEMPERATURE HEATING LOCKOUT
TEMPERATURE (DEGREES F, 0 = DISABLED)
AF H 175 H 50 40 65 SAT COOLING LIMIT SETPOINT (DEGREES F)
AF L 175 L 135 100 180 SAT HEATING LIMIT SETPOINT (DEGREES F)
B0 H 176 H 120 80 180
HYDRONIC HEATING STAGE #1 SUPPLY AIR SETPOINT (DEGREES
F)
B0 L 176 L 150 80 180
HYDRONIC HEATING STAGE #2 SUPPLY AIR SETPOINT (DEGREES
F)
B1 H 177 H 80 60 85 COMFORT VENTILATION UPPER SETPOINT (DEGREES F)
B1 L 177 L 70 60 85 COMFORT VENTILATION LOWER SETPOINT (DEGREES F)
B2 H 178 H 60 40 70
VAV COOLING SUPPLY AIR TEMPERATURE: UPPER SETPOINT
(DEGREES F)
B2 L 178 L 55 40 70
VAV COOLING SUPPLY AIR TEMPERATURE: LOWER SETPOINT
(DEGREES F)
B3 H 179 H 72 40 85
VAV COOLING SUPPLY AIR TEMPERATURE: RESET SETPOINT
(DEGREES F)
B3 L 179 L 68 40 85 VAV OCCUPIED HEATING SETPOINT (DEGREES F)