York YPAL 050 Air Conditioner User Manual


 
134
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
Continued on next page
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
1F H 31 H NA 0 0 255
COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, HIGH
BYTE)
1F L 31 L NA 0 0 255 COMPRESSOR #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
20 H 32 H NA 0 0 255
COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, HIGH
BYTE)
20 L 32 L NA 0 0 255 COMPRESSOR #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
21 H 33 H NA 0 0 255
COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, HIGH
BYTE)
21 L 33 L NA 0 0 255 COMPRESSOR #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
22 H 34 H NA 0 0 255
COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, HIGH
BYTE)
22 L 34 L NA 0 0 255 COMPRESSOR #4 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
24 H 36 H NA 1 1 250 REQUESTED ADDRESS CHANGE (BUS ADDRESS)
26 L 38 L NA NA NA NA REQUESTED OPERATION
0 1 = REQUEST FOR 1ST STAGE COOLING
1 1 = REQUEST FOR 2ND STAGE COOLING
2 1 = REQUEST FOR 3RD STAGE COOLING
3 1 = REQUEST FOR 4TH STAGE COOLING
4 1 = REQUEST FOR 1ST STAGE HEATING
5 1 = REQUEST FOR 2ND STAGE HEATING
6 1 = REQUEST FOR 3RD STAGE HEATING
7 1 = REQUEST FOR FAN
27 H - 33 L
39 H - 51
L
NA
REGISTERS 39 - 51 STORE THE MODEL NUMBER. WHEN
WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER)
SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1
IS IN 39 H. CHARACTER #2 IS IN 39 L. CHARACTER #3 IS IN 40 H,
AND SO ON.
34 H - 40 L
52 H - 64
L
NA
REGISTERS 52 - 64 STORE THE SERIAL NUMBER. WHEN
WRITTEN, ALL 13 REGISTERS (AT 2 BYTES PER REGISTER)
SHOULD BE WRITTEN. THE FORMAT IS ASCII. CHARACTER #1
IS IN 52 H. CHARACTER #2 IS IN 52 L. CHARACTER #3 IS IN 53 H,
AND SO ON.
41 L 65 L NA NA NA NA
REDLINE/LOADSHED STATUS (5 MINUTE TIMER IS STARTED
EACH WRITE. VALUE IS CLEARED IF TIMER IS ALLOWED TO
FINISH.)
0 1 = SET REDLINE OPERATION
1 1 = SET LOADSHED OPERATION
2 - 7 BITS 2-7 UNUSED
42 L 66 L 255 CLEAR LOCKOUT STATUS
WRITE “00” TO CLEAR ALL LOCKOUTS. ANY OTHER VALUE IS
IGNORED. ALWAYS READS 255.
43 H 67 H - 0 255
READING THIS ADDRESS RETURNS EEPROM CHECKSUM HIGH
BYTE