* The 30 dc unregulated supply is not an input. This voltage originates on the microboard and is used to supply the contacts for the binary
inputs.
TABLE 46 MICROBOARD OUTPUTS
TB3-2 SYSTEM 1 COMPRESSOR 1
TB3-3 SYS 1 LIQUID LINE SOLENOID VALVE
TB3-4 SYSTEM 1 COMPRESSOR 2
TB3-5 SYSTEM 1 COMPRESSOR 3
TB3-6 SYSTEM 1 HOT GAS BYPASS VALVE
TB3-8 SYSTEM 2 COMPRESSOR 1
TB3-9 SYS 2 LIQUID LINE SOLENOID VALVE
TB3-10 SYSTEM 2 COMPRESSOR 2
TB4-1 SYSTEM 2 COMPRESSOR 3
TB4-2 SYS 1 CONDENSER FAN STAGE 1
TB4-4 SYS 1 CONDENSER FAN STAGE 2
TB4-5 SYS 1 CONDENSER FAN STAGE 3
TB4-6 SYS 2 CONDENSER FAN STAGE 1
TB4-8 SYS 2 CONDENSER FAN STAGE 2
TB4-9 SYS 2 CONDENSER FAN STAGE 3
TB4-10 EVAPORATOR HEATER
TB5-1 SYSTEM 1 ALARM
TB5-2 SYSTEM 2 ALARM
TB5-3 EVAPORATOR PUMP STARTER
TABLE 44 MICROBOARD BINARY INPUTS
*J9-1 30VDC UNREGULATED SUPPLY
J9-2 UNIT ON/OFF SWITCH
J9-3 PWM TEMP RESET
OR LOAD LIMIT STAGE 2 ON 3 & 6 COMP UNITS
J9-4 LOAD LIMIT STAGE 1
J9-5 FLOW SWITCH AND REMOTE START / STOP
(SYS 1 ZONE THERMOSTAT - YCUL ONLY)
J9-6 SYSTEM 2 ZONE THERMOSTAT - YCUL ONLY
J9-7 SINGLE SYSTEM SELECT
(JUMPER = SINGLE SYS, NO JUMPER=TWO
SYS)
J9-8 CR1 (SYS 1 MOTOR PROTECTOR / HIGH
PRESS CUTOUT)
J9-9 CR2 (SYS 2 MOTOR PROTECTOR / HIGH
PRESS CUTOUT)
TABLE 45 MICROBOARD ANALOG INPUTS
J4-10 Sys 1 Suction Press Transducer or
Sys 1 Low Press Switch
J4-11 SPARE
J4-12 Sys 1 Discharge Pressure Transducer (optional)
J5-12 Sys 1 Suction Temp Sensor - YCUL Option
J5-13 Sys 2 Suction Temp Sensor - YCUL Option
J5-14 SPARE
J5-15 SPARE
J6-7 Ambient Air Temperature Sensor
J6-8 Leaving Chilled Liquid Temperature Sensor
J6-9
Return Chilled Liquid Temperature Sensor
or
Discharge Air Temp Sensor - YCUL Only
J7-10
Sys 2 Suct Press Transducer
or
Sys 2 Low Press Switch
J7-11 SPARE
J7-12 Sys 2 Discharge Pressure Transducer (optional)
J8-5 Sys 1 Ground Fault Circuit
J8-6 Sys 2 Ground Fault Circuit
3