York YCAL0014SC Heat Pump User Manual


 
YORK INTERNATIONAL
30
OPERATIONAL LIMITATIONS (ENGLISH)
YCAL00
LEAVING WATER
COOLER FLOW (GPM
3
) AIR ON CONDENSER (°F)
TEMPERATURE (°F )
MIN
1
MAX
2
MIN MAX MIN
4
MAX
5
14SC 40 55 30 60 25 125
20SC 40 55 30 60 25 125
24SC 40 55 35 70 25 125
30SC 40 55 45 75 25 125
34SC 40 55 75 110 25 125
40SC 40 55 75 250 25 125
44SC 40 55 75 250 25 125
50SC 40 55 75 250 25 125
60SC 40 55 75 250 25 125
64SC 40 55 130 390 25 125
70SC 40 55 130 390 25 125
74SC 40 55 130 390 25 125
80SC 40 55 120 430 25 125
TABLE 7 TEMPERATURES AND FLOWS
NOTES:
1. Standard units cannot be operated below 40°F leaving chilled water temperature.
2. For leaving water temperature higher than 55°F, contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freeze-up to -20.0°F with an electrical heater as standard.
4. Operation below 25°F requires Optional Low Ambient Kit for operation to 0°F.
5. Operation above 115°F requires Optional High Ambient Kit for operation to 125°F.
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and op-
eration beyond these limitations may cause serious dam-
age to the compressor.
TABLE 8 VOLTAGES
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
575-3-60 517 633
Installation
Excessive flow will cause damage to
the cooler. Do not exceed max. cooler
flow. Special care should be taken
when multiple chillers are fed by a
single pump.