York YCAL0014SC Heat Pump User Manual


 
YORK INTERNATIONAL
107
FORM 150.62-NM1
PROBLEM CAUSE SOLUTION
MP / HPCO FAULT 1. Compressor internal motor 1. Verify refrigerant charge is
protector (MP) open. not low. Verify superheat
setting of °10 - 15°F (5.6° -
8.3°C). Verify correct com-
pressor rotation. Verify
compressor is not over
loaded.
2. External overload tripped. 2. Determine cause and reset.
3. HPCO switch open 3. See High Press. Disch.
Fault
4. Defective HPCO switch 4. Replace HPCO switch
5. Defective CR relay 5. Replace relay
COMPRESSOR(S) WONT 1. Demand not great enough. 1. No problem. Consult
START Installation Manual to aid
in understanding compres-
sor operation and capacity
control.
2. Defective water temperature 2. Compare the display with a
sensor. thermometer. Should be
within +/- 2 degrees. Refer
to Service section for RWT/
LWT temp./voltage table.
3. Contactor/Overload failure 3. Replace defective part.
4. Compressor failure 4. Diagnose cause of failure
and replace.
LACK OF COOLING EFFECT 1. Fouled evaporator surface. 1. Contact the local YORK
Low suction pressure will service representative.
be observed.
2. Improper flow through the 2. Reduce flow to within chiller
evaporator. design specs. See Limita-
tions in Installation section.
3. Low refrigerant charge. 3. Check subcooling and add
Low suction pressure will charge as needed.
be observed.
3