DIMENSIONS (ENGLISH)
YCAL0024SC - YCAL0034SC
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated
performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated
below, resulting in unpredictable airflow patterns and possible diminished performance. YORKs unit controls will optimize
operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance
degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended mini-
mum clearances: Side to wall 6'; rear to wall 6'; control panel to end wall 4'; top no obstructions allowed; distance
between adjacent units 10'. No more than one adjacent wall may be higher than the unit.
LD03846
Installation
* Refers to Model YCAL0030SC
** Refers to Model YCAL0034SC