Another anti-recycle timer is started each time the sys-
tems number one compressor cycles off. This anti-re-
cycle time is fixed at 120 seconds and starts to count-
down when the systems number one compressor cycles
off.
The anti-recycle message is displayed when the sys-
tem is unable to start due to either of the anti-recycle
timers being active (counting down). The actual time
displayed will be the longer of the two timers, start-to-
start or stop-to-start.
The Fan Control On Pressure is the programmed pres-
sure value that is used to stage the condenser fans on,
in relation to discharge pressure. Refer to Condenser
Fan Control in the UNIT OPERATION section and
Tables 38, 39, and 40, 41.
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION
section and Tables 38, 39 and 40, 41.
The TOTAL NUMBER OF COMPRESSORS are the
amount of compressors in the chiller, and determines
the stages of cooling available. Notice in Table 29 the
chiller is a single or dual refrigerant circuit.
This must be programmed correctly to
assure proper chiller operation.
TOTAL NUMBER OF
COMPRESSORS = 6
FAN CONTROL ON
PRESSURE= XXXPS IG
FAN DIFFERENTIAL OFF
PRESSURE = XXX PS I G
TABLE 29 PROGRAM KEY LIMITS AND DEFAULTS
PROGRAM VALUE MODEL LOW LIMIT HIGH LIMIT DEFAULT
DISCHARGE PRESSURE CUTOUT
200 PSIG 399 PSIG 395 PSIG
13.8 BARS 27.5 BARS 27.2 BARS
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 PSIG 70.0 PSIG 44.0 PSIG
3.03 BARS 4.83 BARS 3.03 BARS
GLYCOL COOLING
20.0 PSIG 70.0 PSIG 44.0 PSIG
1.38 BARS 4.83 BARS 3.03 BAR
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F 60.0°F 25.0°F
-3.9°C 15.6°C -3.9°C
LOW AMBIENT
0°F 60.0°F 25.0°F
-17.8°C 15.6°C -3.9°C
LEAVING CHILLED LIQUID
WATER COOLING
36°F
2.2°C
TEMP. CUTOUT
GLYCOL COOLING
8.0°F 36.0°F 36.0°F
-13.3°C 2.2°C 2.2°C
ANTI-RECYCLE TIMER 300 SEC. 600 SEC. 600 SEC.
FAN CONTROL ON-PRESSURE
225 PSIG 300 PSIG 230 PSIG
15.5 BARS 20.7 BARS 15.9 BARS
FAN DIFFERENTIAL OFF-PRESSURE
50 PSIG 150 PSIG 80 PSIG
3.45 BARS 10.3 BARS 5.52 BARS
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM 2 3 3
TWO SYSTEMS 4 6 6
2