ELECTRICAL DATA OPTIONAL SINGLE POINT POWER
YCAL0064SC - YCAL0080SC
Installation
TABLE 6 OPTIONAL SINGLE POINT POWER
SINGLE POINT FIELD SUPPLIED WIRING
MODEL
INCOMING WIRE RANGE
6
YCAL
VOLT HZ MCA
1
MIN N/F
D.E. FUSE CKT. BKR.
5
FACTORY SUPPLIED OPTIONAL
DISC SW
2
MIN
3
MAX
4
MIN MAX SINGLE POINT DISCONNECT BREAKER
0064SC
200 60 306 400 350 350 350 350 350 - 500 350 - 500 350 - 500
230 60 284 400 300 300 300 300 300 - 400 300 - 400 300 - 400
380 60 175 200 200 200 200 200 3/0 - 250 3/0 - 250 3/0 - 250
460 60 136 150 150 150 150 150 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
575 60 109 150 125 125 125 125 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
0070SC
200 60 357 400 400 400 400 400 500 - (2) 4/0 500 - (2) 4/0 500 - (2) 4/0
230 60 332 400 350 350 350 350 400 - 600 400 - 600 400 - 600
380 60 201 250 225 225 225 225 4/0 - 300 4/0 - 300 4/0 - 300
460 60 159 200 175 175 175 175 2/0 - 4/0 2/0 - 4/0 2/0 - 4/0
575 60 127 150 150 150 150 150 # 1 - 2/0 # 1 - 2/0 # 1 - 2/0
0074SC
200 60 376 600 400 400 400 400 500 - (2) 4/0 500 - (2) 4/0 500 - (2) 4/0
230 60 349 400 400 400 400 400 500 - (2) 4/0 500 - (2) 4/0 500 - (2) 4/0
380 60 207 250 225 225 225 225 4/0 - 300 4/0 - 300 4/0 - 300
460 60 167 200 175 175 175 175 2/0 - 4/0 2/0 - 4/0 2/0 - 4/0
575 60 134 150 150 150 150 150 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
0080SC
200 60 399 600 450 450 450 450 600 - (2) 250 600 - (2) 250 600 - (2) 250
230 60 371 600 400 400 400 400 500 - (2) 4/0 500 - (2) 4/0 500 - (2) 4/0
380 60 216 250 225 225 225 225 4/0 - 300 4/0 - 300 4/0 - 300
460 60 177 200 200 200 200 200 3/0 - 250 3/0 - 250 3/0 - 250
575 60 142 200 150 150 150 150 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
See notes and legend on pages 18 and 19.