The following messages are displayed when the Sta-
tus key is pressed. Following each displayed message
is an explanation pertaining to that particular display.
GENERAL STATUS MESSAGES
In the case of messages which apply to individual sys-
tems, SYS 1 and, SYS 2 messages will both be dis-
played and may be different. In the case of single sys-
tem units, all SYS 2 messages will be blank.
This message informs the operator that the UNIT switch
on the control panel is in the OFF position which will not
allow the unit to run.
The REMOTE CONTROLLED SHUTDOWN message
indicates that either an ISN or BAS system has turned
the unit off, not allowing it to run.
The DAILY SCHEDULE SHUTDOWN message indi-
cates that the daily/holiday schedule programmed is
keeping the unit from running.
NO RUN PERM shows that either the flow switch is
open or a remote start/stop contact is open in series
with the flow switch.
UNIT SWITCH OFF
SHUTDOWN
REMOTE CONTROL LED
SHUTDOWN
DA I LY SCHEDULE
SHUTDOWN
FLOW SWITCH/REM STOP
NO RUN PERMI SS IVE
00066VIP
Unit Controls