Troubleshooting control moduleXIe
Control Module
Make sure ground wiring is installed per wiring diagram.
Good grounding is extremely important for proper
operation.
Solder or water splatter between
plugs and circuit board can cause
improper operation of control
module. Place a shield over the boiler
internal controls and components
during installation. Failure to comply
could result in severe personal injury,
death or substantial property
damage.
85063
Non-lockout light conditions
TSTAT CIRC light flashing alone
Usually indicates return water temperature sensor detects
water at boiler return pipe less than 40 °F. Both internal
circulators will run continuously, even with no call for
heat, until temperature rises.
LIMIT light flashing alone
Usually indicates an open or shorted return water
temperature sensor.
Troubleshooting the GCM
See Figure 34 for location of harness plug receptacles and
plugs on the control module.
Control indicator lights
lockout modes
See Charts 1 through 8 in this section for detailed trouble-
shooting procedures.
To reset control after a lockout, turn off power at the 120
VAC service switch or turn down all thermostats. Wait 45
seconds. Then restore power or call for heat.
After an over-temperature lockout (POWER and LIMIT
lights flashing), the control will only reset after
interruption of 120 VAC for 45 seconds. (And temperature
at return water temperature sensor must be below 240 °F. )
POWER light flashing alone
Usually indicates reversed polarity of 120 VAC power
wires.
POWER and TSTAT CIRC lights flashing
Usually indicates stray voltage on external thermostat
circuit wires or return water temperature entering boiler
sections has not reached 130 °F within 20 minutes.
POWER and LIMIT light flashing alternately
Usually indicates that limit circuit failed to cut off boiler
at high temperaure return water temperature sensor
has sensed water over 235 °F.
POWER and PRES SWITCH lights flashing
Usually indicates pressure switch is closed when it should
not be, or pressure switch failed to close within 5 minutes
of blower starting.
POWER and FLAME lights flashing
Usually indicates control has had three unsuccessful
ignition attempts or sensed flame when it shouldnt be
there.