Weil-McLain 550-141-850/0599 Boiler User Manual


 
35Part number 550-141-850/0699
Installation Start-Up Parts Maintenance
Water piping snow melt systemIIIi
Figure 15b Auto return temp regulation; for
outdoor reset or fixed temp
Heating zone(s)
85016
Cold
water
fill
GV Boiler
12"
max
Snow melt
heat exchanger
Figure 15a Manual bypass valves; for fixed
temp operation only
Heating zone(s)
85014b
Cold
water
fill
GV Boiler
12"
max
Snow melt
heat exchanger
Legend
1 Boiler isolation valves
2 Automatic air vent (with diaphragm-type
expansion tank), or connect to tank fitting
(closed-type expansion tank).
3 Diaphragm- or bladder-type expansion tank, if
used (For closed-type expansion tank, pipe
from top of air separator to tank fitting as in
Figure 10.)
4 Zone valve
5 System or zone circulator
6 Flow/check valve
7 Hose bibb purge valve
8 Boiler pressure/temperature gauge
9 System supply temperature gauge
12 Return temperature automatic mixing valve
Piping snow melt systems or
combination snow melt/
space heating systems
Combination snow melt/space heating systems will have
widely varying system return temperatures. So these
systems require automatic return water temperature as
shown in Figure 15a (zone-valve zoning) or Figure 15b
(circulator zoning).
Select an automatic temperature control valve or motor-
operated valve which can be adjusted to provide a return
water temperature of at least 60 °F. Any setting higher
than 60 °F will also be acceptable.
Zone-valve zoning The suggested piping uses a separate
circulator for system circulation to assure good
temperature distribution in the system when the return
water temperature is low.
Circulator zoning The GV internal circulators must
not be removed. Provide a separate circulator for each
zone.
The return water temperature to the
boiler must be at least 60 °F. Provide
and apply means to regulate the
return temperature. Failure to do so
can result in boiler control operation
problems, causing possible
significant property damage.