The illustration below shows coupler wiring.
Figure 5-10. Coupler Wiring
Refer to the guidelines and figures in this topic to use wired media cards.
IMPORTANT: TB1 on the wired media card must not be used when it is
connected to the 4100-6014 NIC.
When the 565-413 Interface Card is used with 565-516, -407, or –409 Network
Card, TB1 on the 565-413 Interface Card cannot be used. Connection to the
motherboard is required as shown.
The shield should only be connected at one end of the line. The shield is
connected to the left port.
When wiring leaves the building, 2081-9044 Overvoltage Protectors are
required. One overvoltage protector is installed where wiring leaves the building;
another is installed where wiring enters the next building.
Continued on next page
Step 4. Wiring Network Cards, Continued
4190-9010 Coupler
Requirements
(continued)
Wiring with the
Wired Media Card