Tyco 4100U Smoke Alarm User Manual


 
H-1
System Capacity 2,000 points of addressable points, plus 2,000 points of
annunciation. Expansion Up to capacity above.
Up to 119 Addressable cards
Cabinet Size Dependent on system configuration
Cabinet Material 1.6mm Zintex
Cabinet Finish Powder coated
Cabinet Colour Cream Wrinkle
Mounting Wall mount
Mains Input 240V AC, +6%, -10%, 50Hz
Internal Power Supply 24V DC @ 9A
Standby Battery 24V sealed lead acid up 110Ah
Battery Charger 27.3V DC (nominal)
PSU Supervision Charger high/low, Battery low/fail
Temperature -5°C to 45°C
Humidity 10% to 90% RH non-condensing
Refer to Table 6-1, 6-2 for full SPS specifications.
Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board (if fitted)
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
WALK TEST System Test
4 Operator Access Levels
Event Historical Logging
Device selectable Alarm Verification
Individual Zone Isolate
Addressable device disable/enable
Non-volatile Flash EPROM for field editable program changes
Expansion cards firmware upgraded via download to flash EPROMs
Appendix H
4100U Specifications
General
Fuses
Firmware Features