Tyco 4100U Smoke Alarm User Manual


 
7-6
Table 7-1 lists the maximum distances from the NAC terminal block to the last appliance
in a Class A configuration, depending on wire gauge and current. Use Table 7-1 to
calculate wire distances for your application if you are using Class A wiring.
Table 7-1. Class A Wiring Distances
Alarm
Current @
24 V
Max Distance
w/ 18 AWG
(0.8231 mm
2
)
Max Distance
w/ 16 AWG
(1.309 mm
2
)
Max Distance
w/ 14 AWG
(2.081 mm
2
)
Max Distance
w/ 12 AWG
(3.309 mm
2
)
DC
Resistance
0.25 A 420 ft. (128 m) 667 ft. (203
m)
1,063 ft. (324
m)
1,691 ft. (515
m)
6 Ohms
0.50 A 210 ft. (64 m) 334 ft. (102
m)
532 ft. (162 m) 845 ft. (258 m) 3 Ohms
0.75 A 140 ft. (43 m) 222 ft. (68 m) 354 ft. (108 m) 564 ft. (172 m) 2 Ohms
1 A 105 ft. (32 m) 167 ft. (51 m) 266 ft. (81 m) 423 ft. (129 m) 1.5 Ohms
1.25 A 84 ft. (26 m) 133 ft. (41 m) 213 ft. (65 m) 338 ft. (103 m) 1.2 Ohms
1.50 A 70 ft. (21 m) 111 ft. (34 m) 177 ft. (54 m) 282 ft. (86 m) 1 Ohm
1.75 A 60 ft. (18 m) 95 ft. (29 m) 152 ft. (46 m) 242 ft. (74 m) 0.86 Ohm
2 A 53 ft. (16 m) 83 ft. (25 m) 133 ft. (41 m) 211 ft. (64 m) 0.75 Ohm
2.25 A 47 ft. (14 m) 74 ft. (23 m) 118 ft. (36 m) 188 ft. (57 m) 0.67 Ohm
2.50 A 42 ft. (13 m) 67 ft. (20 m) 106 ft. (32 m) 169 ft. (51 m) 0.60 Ohm
2.75 A 38 ft. (12 m) 61 ft. (19 m) 97 ft. (30 m) 154 ft. (47 m) 0.55 Ohm
3 A 35 ft. (11 m) 56 ft. (17 m) 89 ft. (27 m) 141 ft. (43 m) 0.50 Ohm
Notes:
Max Distance = distance from SPS/RPS to last appliance.
This table is calculated at 49 degrees Centigrade (120 degrees
Fahrenheit). If you are installing in locations that could be exposed to
higher temperatures, refer to NEC Tables 7 and 8 in NFPA code, or
applicable local standard.
Distances are based on a 3 V drop, and take into account the worst-case
panel output voltage. These distances are worst case to allow for one
single load at the furthest point.
If circuit integrity wire is used instead of housing cable in a fire-rated
enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3
m) of potential exposure.
For other wire gauges (e.g. 4 mm
2
) multiply the distance specified for the
nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm
2
look
up 3A on 12AWG (3.3 mm
2
) and multiply the resulting 43m x 4.0/3.3 =
52m.
Continued on next page
Class A NAC
Wiring Table