Tyco 4100U Smoke Alarm User Manual


 
6-2
The following table summarizes the specifications for the SPS.
Table 6-1. SPS Input and Output Specifications
AC Input Specifications
SPS in Standard
Australian FACP
4100-9848AU
2 A Maximum
240 VAC + 6% -10% @ 50 Hz
DC Output Specifications
Voltage
Nominal 28VDC
Minimum: 19.5 VDC Maximum: 32 VDC
Ripple: 2 VDC p-p @ full load (9A)
Total Current (max)
24V Card
24V Aux
Each NAC (total A+B)
9A alarm load. Includes: NACs (+24V Sig);
+24V Card; +24V Aux; SPS card power
including on-board IDNet.
5A non-alarm load. Includes as per above,
allows for battery charging at high rate.
2A max. See note.
2A max
3A max alarm load
2A max non-alarm load (used as Aux 24V
power).
SPS IDNet Output 30 V or 35 V (see note below)
Battery Charger Specifications
Input Voltage Range 21-33 VDC
Output Float Voltage
27.3 VDC ±200 mV @ 20°C, temperature
compensated at approximately -36mV/°C
(0° C to 50° C)
Output Current Limit
1.4 A (For 6.2 – 18 Ah battery)
3.3 A (Default; for 18-110 Ah battery)
Notes:
AC power must be provided to the 4100U from a dedicated AC branch circuit.
The AC input is supervised.
240 VAC: The service branch circuit breaker should be sized to handle at
least 150 percent of the total required by all of the power supplies in the
system.
The bulk supply (rated at 9A max) which feeds 24V Sig, 24V Card, 24V Aux
also supplies the SPS Card including the on board IDNet, and the battery
charger. The charger is disabled during alarms so as to make the 9A
available on the other busses. (See the following table for the SPS current.)
Continued on next page
SPS Specifications
Input/Output/Battery
Specifications