Trane 3RT-PRC005-EN Air Conditioner User Manual


 
65
RT-PRC005-EN
Electrical
Data
(High
Efficiency)
Table ED-2 — Unit Wiring — High Efficiency
Optional
Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor
2
Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
THC036A1 187-253 23.9 40 26.3 40 N/A N/A
3 THC036A3 187-253 17.2 25 19.6 30 19.9 30
THC036A4 414-506 9.0 15 10.2 15 10.4 15
THC036AW 517-633 7.1 15 7.7 15 7.7 15
THC048A1 187-253 29.4 45 31.5 50 N/A N/A
THC048A3 187-253 21.2 30 23.3 35 22.6 35
4 THC048A4 414-506 11.0 15 12.6 15 11.8 15
THC048AW 517-633 8.3 15 9.1 15 8.5 15
THC060A1 187-253 39.5 60 41.2 60 N/A N/A
THC060A3 187-253 30.0 45 31.7 45 28.8 45
5 THC060A4 414-506 14.7 20 15.0 20 14.3 20
THC060AW 517-633 11.8 15 12.4 15 11.4 15
THC072A3 187-253 34.8 50 36.1 50
6 THC072A4 414-506 17.5 25 18.1 25
THC072AW 517-633 13.5 20 14.3 20
THC092A3 187-253 38.1 50 41.2 50
THC092A4 414-506 19.4 25 20.9 25
THC092AW 517-633 14.8 15 16.0 20
THC102A3 187-253 42.3 50 45.4 60
THC102A4 414-506 21.4 25 22.9 30
THC102AW 517-633 16.6 20 17.8 20
THC120A3 187-253 48.6 60 52.6 60
10 THC120A4 414-506 25.3 30 27.3 35
THC120AW 517-633 19.9 25 21.6 25
Notes:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.