Trane 3RT-PRC005-EN Air Conditioner User Manual


 
73
RT-PRC005-EN
Electrical
Data
(High
Efficiency)
Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — High Efficiency
Belt Drive Indoor Motor
To Use Heater Heater Control Max Fuse Size or
Tons With Model No. kW Rating
1
Stages MCA Max Circuit Breaker
2
208/230 Volts Single Phase
BAYHTRR105A N/A N/A N/A N/A
3 THC036A1 BAYHTRR110A N/A N/A N/A N/A
BAYHTRR114A N/A N/A N/A N/A
BAYHTRR105A N/A N/A N/A N/A
BAYHTRR110A N/A N/A N/A N/A
4 THC048A1 BAYHTRR114A 1N/A N/A N/A N/A
BAYHTRR118A N/A N/A N/A N/A
BAYHTRR105A N/A N/A N/A N/A
BAYHTRR110A N/A N/A N/A N/A
5 THC060A1 BAYHTRR114A N/A N/A N/A N/A
BAYHTRR118A N/A N/A N/A N/A
208/230 Volts Three Phase
BAYHTRR306A 4.5/6.0 1 21.9/24.3 25/25
3 THC036A3 BAYHTRR312A 9.0/12.0 2 37.5/42.4 40/45
BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR306A 4.5/6.0 1 22.6/24.3 35/35
4 THC048A3 BAYHTRR312A 9.0/12.0 2 37.5/42.4 40/45
BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR306A 4.5/6.0 1 28.8/28.8 45/45
BAYHTRR312A 9.0/12.0 2 37.5/42.4 45/45
5 THC060A3 BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR323A 17.3/23.0 2 66.3/75.4 70/80
460 Volts Three Phase
BAYHTRR406A 6.0 1 12.1 15
3 THC036A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR406A 6.0 1 12.1 15
4 THC048A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR406A 6.0 1 14.3 20
5 THC060A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR423A 23.0 2 37.8 40
575 Volts Three Phase
BAYHTRRW06A 6.0 1 9.3 15
3 THC036AW BAYHTRRW12A 12.0 2 16,6 20
BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW06A 6.0 1 9.3 15
4 THC048AW BAYHTRRW12A 12.0 2 16.6 20
BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW06A 6.0 1 11.4 15
BAYHTRRW12A 12.0 2 16.6 20
5 THC060AW BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW23A 23.0 2 29.8 30
Notes:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.