Trane 3RT-PRC005-EN Air Conditioner User Manual


 
52 RT-PRC005-EN
(7½ Ton)
High Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-56.
Table includes Dehumidification (Hot Gas Reheat Option).
*Unit applications below 2400 CFM
Electric heaters restricted on applications below 2400 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 2400 CFM.
Notes:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
No accessories or options are included in pressure drop data.
Refer to Table PD-61 to determine additional static pressure drop due to other options/accessories
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. BAYLSDR009A Required.
2. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-51 — Belt Drive Evaporator Fan Performance — 7½ Ton — THC092A3,A4,AW—Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit (1)
1500* 509 0.26 558 0.32 601 0.39 640 0.45 678 0.52 715 0.59 750 0.67 783 0.75
1800* 472 0.24 542 0.34 597 0.42 640 0.50 678 0.58 714 0.65 748 0.73 780 0.81 811 0.89
2100* 511 0.33 568 0.42 628 0.52 678 0.63 718 0.72 754 0.81 787 0.90 817 0.99 846 1.08
2400 502 0.36 552 0.43 603 0.52 653 0.63 707 0.75 754 0.88 792 0.99 825 1.09 857 1.19 886 1.30
2700 554 0.49 595 0.56 644 0.66 686 0.77 732 0.89 780 1.03 824 1.17 863 1.30 895 1.42 925 1.54
3000 605 0.65 644 0.73 684 0.82 726 0.94 765 1.06 806 1.20 849 1.35 891 1.51 929 1.66 962 1.80
3300 658 0.84 694 0.93 728 1.02 767 1.15 805 1.28 840 1.40 876 1.55 916 1.71 955 1.89 991 2.06
3600 711 1.07 746 1.18 776 1.27 809 1.38 846 1.52 880 1.66 912 1.80 943 1.95 980 2.13 1016 2.30
2-HP Standard Motor & Drive
Table PD-51 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
1500* 815 0.83 847 0.91 876 0.99 904 1.07 932 1.16 958 1.25 985 1.34 1009 1.43 1033 1.51 1057 1.61
1800* 842 0.98 872 1.07 901 1.16 929 1.25 957 1.35 983 1.44 1008 1.54 1034 1.64 1058 1.74 1081 1.84
2100* 876 1.18 904 1.27 931 1.36 956 1.46 982 1.55 1008 1.66 1034 1.77 1059 1.87 1083 1.99 1107 2.10
2400 913 1.40 941 1.51 966 1.61 991 1.71 1017 1.82 1040 1.92 1064 2.04 1087 2.14 1110 2.26 1132 2.37
2700 954 1.66 981 1.77 1006 1.89 1030 2.00 1054 2.12 1077 2.24 1100 2.36 1121 2.47 1144 2.60 1164 2.71
3000 992 1.94 1019 2.07 1045 2.20 1069 2.32 1094 2.46 1116 2.58 1138 2.71 1160 2.84 1181 2.97 1202 3.10
3300 1025 2.22 1055 2.38 1082 2.53 1108 2.67 1132 2.82 1156 2.96 1178 3.11 1200 3.25 1221 3.39
3600 1052 2.50 1085 2.69 1117 2.88 1144 3.05 1170 3.21 1193 3.37 ———————
3-HP Oversized Motor & Drive